| General |
| Topology |
Line-Interactive High Frequency (Pure Sinewave, Booster + Fader) |
| Configuration |
Tower/Rack 2U |
| Part Number |
5PX1500iRT |
| Rating (VA/Watts) |
1500/1350 |
| Dimensions (H x W x D, mm) |
86.2 x 441 x 522 |
| Weight (kg) |
28 |
| |
| Electrical Input |
| Connection |
(1) IEC-320-C14

|
| Input Voltage Without Using Batteries |
160V-294V (adjustable to 150V-294V) |
| Input frequency Range Without Using Batteries |
47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system), 40 Hz in low-sensitivity mode |
| |
| Electrical Output |
| Voltages |
230 V (+6/-10 %) (Adjustable to 200V / 208V / 220V / 230V / 240V) |
| Outlets |
(8) IEC-320-C13

|
| Remotely controlled sockets |
2 groups of 2 x IEC C13 (10 A) |
| Output Frequency |
50/60 Hz +/- 0.1 % (autosensing) |
| |
| Battery |
Runtime (Minutes)
200
400
600
800
1000
1200
0
100
200
300
400
500
600
700
800
900
1000
|
|
Standard Runtime |
|
|
With 1 EBM |
|
|
With 2 EBMs |
|
|
With 3 EBMs |
|
|
With 4 EBMs |
Load (Watts)
Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc. Actual runtime may vary from +/- 15% around these typical values
|
| Battery Management |
ABM® & Temperature compensated charging method (user selectable), Automatic battery test, deep discharge protection, automatic recognition of external battery units |
| |
| Communications |
| Communication Ports |
1 USB port + 1 RS232 serial port and relay contacts (USB and RS232 ports cannot be used simultaneously) + 1 mini terminal block for remote ON/OFF and Remote Power Off |
| Communications Card Slots |
1 slot for NMC Minislot card or NMC ModBus/JBus or MC Contacts/Serial |
| |
| Environmental & Standards |
| Audible Noise |
< 45 dBA |
| Operating Temperature |
0 to 40°C |
| Performance - Safety - EMC |
IEC/EN 62040-1-1 (Safety), IEC/EN 62040-2 (EMC), IEC/EN 62040-3 (Performance), |
| Approvals |
CE, CB report, TÜV |
| |
| |
| |
|